Alarm Inbox

9 alarms · 5 unacknowledged
C₂H₂ rise on T2 — possible arcing in oil
T2 · INSIDEVIEW 6.0 · Duval Triangle
Unack
22m ago
Site offline · Longleaf PQ
pq-site-05-dstat · Edge heartbeat
UnackCasey Park
14h ago
Breaker 52F24 auto-tripped
52F24 · SEL-351 · 51P
UnackT. Sabat
8h ago
IGBT over-temp · Sauk Prairie D-STATCOM
pq-site-04-dstat · Fleet benchmark · peer anomaly
Unack
14h ago
Bushing PF drift · T1 LV-B
T1 · doblePRIME Expert System
ACK
4h ago
Winding hot-spot T2 above 90 °C
T2 · IEEE C57.91
ACK
1d ago
DC bus float voltage low
SG_A_T2.Battery · SEL battery monitor
ACK
2d ago
THD drifting · Hartford PQ
pq-site-03-dstat
Unack
3d ago
H₂ baseline shift on T3
T3
ACK
4d ago

C₂H₂ rise on T2 — possible arcing in oil

CRITICAL
· raised 22m ago · source INSIDEVIEW 6.0 · Duval Triangle · stream T2.dga.c2h2
Acetylene climbed from 0.4 ppm → 2.3 ppm over last 14 days. Duval Triangle zone shifted D1 → D2 (high-energy arcing).
Pre-event trace · T2.dga.c2h2last 36 samples